RE-2G(St)HSWAH-CI-TIMF FE180 HALOGEN-FREE FIRE RESISTANT (CI) INSTRUMENTATION CABLES, EN 50288-7 MULTI-TRIPLE, SILICONE INSULATED, INDIVIDUAL & COLLECTIVE SCREENED, ARMOURED, HFFR SHEATHED
Marking
BIRTAS KABLO RE-2G(St)HSWAH-Cl TIMF FE 180 6 x 3 x 1.5mm2 2626 45 006 (HFFR) 90˚ C 500 V EN 50288-7 IEC 60331 Part no GOST-R CE..mt
Applications
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... These cables are used on the basis of a fixed operating mode, can continue with the supply of a power under the existing fire conditions and in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Cable Design
Conductor
Plain copper wire, stranded IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation
Special silicone rubber compound
Core identification
Black / Blue / Red; with numbered tape under separator tape of the pair screen Upon request ; Black / Blue / Red cores numbered 1-1-1, 2-2-2,… Other core configurations manufactured upon request.
Triple
Three conductors twisted to a triple
TIMF Construction
Polyester tape above the triple, AL-PES tape over solid tinned copper drain wire, 0,60 mm Upon request ; Stranded 0,50 mm2 copper drain wire
Lay-up
TIMF laid up in layers of optimum pitch
Separator
Polyester tape
Screen
AL-PES tape over stranded tinned copper drain wire 0,50 mm2