Halogen Free Installation & Energy Cables
H05Z-U & H07Z-U/R & H05Z/K & H07Z/K
H05Z1-U & H07Z1-U/R & H05Z1/K & H07Z1/K
H03Z1Z1-F 300/300 V & H05Z1Z1-F 300/500 V
NHMH
NHXMH
N2XH
N2XCH
NHXMH FE180
N2XH FE180
(N)2GH FE180
(N)2GH FE180 - FLEX
(N)HXH FE180 E30
(N)HXH FE180 E90
(N)HXCH FE180 – E30
(N)HXCH FE180 – E90
Cu/XLPE/LSZH/SWA/LSZH – MULTICORE – BS 6724
2XHRH
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
ISTINYE PARK SHOPPING CENTER
KORUPARK SHOPPING CENTER
FORUM MERSİN SHOPPING CENTER
CEPA SHOPPING CENTER
KANYON SHOPPING CENTER
ISTANBUL TEKSTİLKENT
HALOGEN FREE INSTALLATION & ENERGY CABLES
2XHRH
HALOGEN-FREE, ARMOURED ENERGY CABLES, 0,6/1 kV
Marking

BIRTAS KABLO 2XHRH 5 x 2.5 (rm) mm2 1999 46 005 Part no GOST-R CE … mt

Applications

These armoured halogen-free cables are used as energy, utility and lighting cables in dry, moist and wet rooms, for permanent installation indoor and outdoor applications where lots of human life and material assets are to be protected in industrial constructions, schools, hospitals, shopping and cultural centers,energy plants, airports, metros . The armour above the inner sheath protects the cable from mechanical shocks. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

Cable Design
ConductorCu wires,plain, solid-core, multi-stranded
IEC 60228 Cls. 1/2, TS/DIN EN 60228 Cls. 1/2
InsulationXLPE compound
Core identificationAccording to TS HD 308 S2 & VDE 0293-308;
Note: Other core configurations manufactured upon request.
Lay-upCores laid up in layers of optimum pitch
FillerHFFR filler compound
ArmourGalvenised steel wire, helically
Outer sheathHFFR compound, HM4, VDE 0276-604
HFFR: Halogen-free flame retardant
Sheath colourRAL 9005, Black
Technical Data
StandardIEC 60502-1
Temp. at conductor90 oC
Rated voltage0,6 / 1 kV
Test voltage3500 V
Temperature rangeFixed: - 30 oC ~ + 90 oC
Min. bending radius≤ 16mm2 : 6 x D
≥ 25mm2 : 8 x D
Flame testIEC 60332-3 & TS/DIN EN 50266-2-4
Smoke density testIEC 61034-2 & TS/DIN EN 61034-2
Halogen-free properties testIEC60754-1/2 & TS/DIN EN 50267-2
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1999 45 0022x1,5-rm12,829355
1999 45 0033x1,5-rm13,243385
1999 45 0044x1,5 –rm14,158435
1999 45 0055x1,5-rm15,172500
1999 46 0022x2,5-rm14,348445
1999 46 0033x2,5-rm14,872490
1999 46 0044x2,5-rm 15,696555
1999 46 0055x2,5-rm 16,8120645
1999 47 0022x4-rm15,577530
1999 47 0033x4-rm 16,0115610
1999 48 0022x6-rm 16,6115640
1999 47 0044x4-rm 17,1154695
1999 47 0055x4-rm 19,2192715
1999 48 0033x6-rm 17,4173735
1999 48 0044x6-rm 19,7230770
1999 49 0022x10-rm 18,7192825
1999 49 0033x10-rm 20,4288845
1999 48 0055x6-rm21,1288890
1999 50 0022x16-rm21,8192950
1999 49 0044x10-rm 21,93841010
1999 50 0033x16-rm 23,12881190
1999 49 0055x10-rm23,94801225
1999 51 0022x25-rm 25,71921365
1999 50 0044x16-rm 24,83841410
1999 50 0055x16-rm28,17681625
1999 51 0033x25-rm 28,42881645
1999 51 0044x25-rm 30,43841990
1999 51 0055x25-rm33,212002410