BIRTAS KABLO LSPYCY 4 x 2 x 1.5mm2 1121 08 004 Part no GOST-R CE … mt
Applications
These screened cables are used in dry, damp and wet locations.In case protected from direct sun light, outdoor fixed installations. In machines and automation industry, in which process data operations and measurement values used, as control and signal cable. As fixed and flexible cables, in systems, where high mechnical pulling forces and indispensable movements are not existing. And also consisting of tinned copper wires as screen provides protection against external pulses and ensures an interference-free transmission and signal cable. As fixed and flexible cables, in systems, where high mechnical pulling forces and indispensable movements are not existing.
Cable Design
Conductor
Flexible copper wires, plain; IEC 60228 Class 5, TS/DIN EN 60228 Class 5
Insulation
PVC compound , YI2 VDE 0207-4
Core identification
According to DIN 47100 or TS/DIN EN 50334 black cores with white numerals
Pair
Two conductors twisted to a pair
Lay-up
Pairs laid up in layers of optimum pitch
Separator
Polyester tape
Outer sheath
PVC compound, YM1, VDE 0207-5
Screen
Braid of tinned Cu wires, 85% coverage
Outer Colour
RAL 7032,Grey
Technical Data
Standard
VDE 0245
Insulation resistance
Min. 20 MΩ.km
Rated voltage Uo/U
300 / 300V
Test voltage (AC 50 Hz)
2000 V
Current carrying capacity ( in air )
0,50 mm2: 9,5 A ; 0,75 mm2: 12 A ; 1,0 mm2: 15 A ; 1,5 mm2: 18 A