background
TR  EN  DE  RU

Products

Back to products list
Birtaş Kablo
Instrumentation Cable
Flame Retardant
RE-2G(St)H-CI FE180 MP
RE-2G(St)H-CI FE180
RE-2G(St)H-CI-PIMF FE180
RE-2G(St)H-CI-TIMF FE180
RE-2G(St)HSWAH-CI FE180 MP
RE-2G(St)HSWAH-CI FE180
RE-2G(St)HSWAH-CI-PIMF FE180
RE-2G(St)HSWAH-CI-TIMF FE180
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
MODERN CARTON
TÜPRAS
DOLPHIN PROJECT
ISKENDERUN STEEL
COLAKOGLU METALURJİ
PASABAHCE GLASS
INSTRUMENTATION CABLES
500V - Yangına Dayanıklı
RE-2G(St)H-CI FE180
HALOGEN-FREE FIRE RESISTANT (CI) INSTRUMENTATION CABLES, EN 50288-7
SINGLE & MULTI-TRIPLE, SILICONE INSULATED, COLLECTIVE SCREENED, HFFR SHEATHED
Marking

BIRTAS KABLO RE-2G(St)H-Cl FE 180 2 x 3 x 0.75mm2 2620 42 002 (HFFR) 90˚ C 500 V EN 50288-7 IEC 60331 Part no GOST-R CE....mt

Applications

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... These cables are used on the basis of a fixed operating mode, can continue with the supply of a power under the existing fire conditions and in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

Cable Design
ConductorPlain copper wire, stranded
IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
InsulationSpecial silicone rubber compound
Core identificationBlack / Blue / Red cores are numbered
(1-1-1, 2-2-2,…)
Upon request ; Colour coded according to IEC 60189-2
Other core configurations manufactured upon request.
TripleThree conductors twisted to a triple
Lay-upTriples laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenAL-PES tape over stranded tinned copper drain
wire 0,50 mm2
Outer sheathHFFR compound, EN 50290-2-27
Sheath colourRAL 9005, Black or RAL 5015, Blue
Technical Data
StandardTS/DIN EN 50288-7
(Designed according to)
Conductor resistance0,50mm2 : 36,7 Ω/km
0,75mm2 : 25,0 Ω/km
1,0mm2 : 18,5 Ω/km
1,3mm2 : 14,2 Ω/km
1,5mm2 : 12,3 Ω/km
Insulation resistanceMin. 5000 MΩ.km
Mutual Capacitance0,50 mm2 : max. 150 pF/m ≤ 4 pairs,max. 100 pF/m all other pairs
0,75 mm2 : max. 150 pF/m ≤ 4 pairs,max. 100 pF/m all other pairs
1,0 mm2 : max. 150 pF/m ≤ 4 pairs,max. 100 pF/m all other pairs
1,3 mm2 : max. 165 pF/m ≤ 4 pairs,max. 120 pF/m all other pairs
1,5 mm2 : max. 165 pF/m ≤ 4 pairs,max. 120 pF/m all other pairs
Capacitance unbalance (1 kHz) : max. 500 pF/500 m
L / R (ratio) (max.)0,50mm2 : 25 µH/Ω
0,75mm2 : 25 µH/Ω
1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω
1,5mm2 : 40 µH/Ω
Rated voltage500V
Test voltageUrms core-core : 2000 V
Urms core-screen : 2000 V
Temperature rangeoperation : - 30 oC ~ + 90 oC
ınstallation : - 5 oC ~ + 50 oC
Min. bending radius7,5 x D
Flame testIEC 60332-1 & TS/DIN EN 60332-1
IEC 60332-3 & TS/DIN EN 50266-2-4
Smoke density testIEC 61034-2 & TS/DIN EN 61034-2
Halogen-free properties testIEC60754-1/2 & TS/DIN EN 50267-2
Circuit integrity (CI)IEC 60331 , VDE 0472-814
BS 6387 Cat. CWZ
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
2620 41 0011x3x0,506,71960
2620 41 0022x3x0,5010,534105
2620 41 0044x3x0,5012,362170
2620 41 0055x3x0,5013,277200
2620 41 0066x3x0,5014,491240
2620 41 0088x3x0,5016,4120310
2620 41 01010x3x0,5018,0149375
2620 41 01212x3x0,5019,6178445
2620 41 01616x3x0,5022,4235580
2620 41 02020x3x0,5024,8293710
2620 41 02424x3x0,5027,1350845
2620 42 0011x3x0,757,32670
2620 42 0022x3x0,7511,948135
2620 42 0044x3x0,7513,991225
2620 42 0055x3x0,7514,9113270
2620 42 0066x3x0,7516,3134320
2620 42 0088x3x0,7518,3177405
2620 42 01010x3x0,7520,4221500
2620 42 01212x3x0,7522,2264595
2620 42 01616x3x0,7525,3350775
2620 42 02020x3x0,7528,1437955
2620 42 02424x3x0,7530,65231135
2620 43 0011x3x17,53480
2620 43 0022x3x112,362155
2620 43 0044x3x114,4120260
2620 43 0055x3x115,4149310
2620 43 0066x3x116,8178365
2620 43 0088x3x119,2235480
2620 43 01010x3x121,1293580
2620 43 01212x3x123,0350690
2620 43 01616x3x126,2466900
2620 43 02020x3x129,15811110
2620 43 02424x3x131,76961320
2620 44 0011x3x1,38,14295
2620 44 0022x3x1,313,180180
2620 44 0044x3x1,315,3155305
2620 44 0055x3x1,316,6192375
2620 44 0066x3x1,317,9230440
2620 44 0088x3x1,320,5304570
2620 44 01010x3x1,322,7379705
2620 44 01212x3x1,324,7454840
2620 44 01616x3x1,328,26041095
2620 44 02020x3x1,331,37541350
2620 44 02424x3x1,334,19031605
2620 45 0011x3x1,58,448100
2620 45 0022x3x1,513,791200
2620 45 0044x3x1,515,8177335
2620 45 0055x3x1,517,1220410
2620 45 0066x3x1,518,5264480
2620 45 0088x3x1,521,1350625
2620 45 01010x3x1,523,4436770
2620 45 01212x3x1,525,5523920
2620 45 01616x3x1,529,16961205
2620 45 02020x3x1,532,58681500
2620 45 02424x3x1,535,410411785
Top 