background
TR  EN  DE  RU

Products

Back to products list
Birtaş Kablo
Instrumentation Cables BS 5308
RE-2Y(St)Y-fl-MP
RE-2Y(St)Y-fl-PIMF
RE-2Y(St)Y-fl
RE-2Y(St)Y-fl-TIMF
RE-2Y(St)2YSWAY-fl-MP
RE-2Y(St)2YSWAY-fl-PIMF
RE-2Y(St)2YSWAY-fl
RE-2Y(St)2YSWAY-fl-TIMF
RE-Y(St)Y-fl
RE-Y(St)Y-fl-MP
RE-Y(St)Y-PIMF
RE-Y(St)YSWAY-fl
RE-Y(St)YSWAY-fl-MP
RE-Y(St)YSWAY-PIMF
RE-2Y(St)H & RE-2X(St)H-MP
RE-2Y(St)H & RE-2X(St)H
RE-2Y(St)H-PIMF & RE-2X(St)H-PIMF
RE-2Y(St)H-TIMF & RE-2X(St)H-TIMF
RE-2Y(St)HSWAH & RE-2X(St)HSWAH
RE-2Y(St)HSWAH &
RE-2X(St)HSWAH-MP
RE-2Y(St)HSWAH-PIMF &
RE-2X(St)HSWAH-PIMF
RE-2Y(St)HSWAH-TIMF &
RE-2X(St)HSWAH-TIMF
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
MODERN CARTON
TÜPRAS
DOLPHIN PROJECT
ISKENDERUN STEEL
COLAKOGLU METALURJİ
PASABAHCE GLASS
INSTRUMENTATION CABLES BS5308
RE-Y(St)YSWAY-PIMF
INSTRUMENTATION CABLES, BS 5308 PART 2 TYPE 2
MULTİ-PAİR, PVC INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, ARMOURED PVC SHEATHED
Marking

BIRTAS KABLO RE-Y(St)YSWAY-fl PİMF 10 x 2 x 1.5mm2 1614 45 010 BS 5308 Part no GOST-R CE....mt

Applications

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

Cable Design
ConductorPlain annealed copper wire, BS 6360
0,50 mm2 and 0,75 mm2 flexible, or
1,5 mm2 stranded
InsulationPVC compound, TI1, BS 6746
Core identificationWhite / blue ; with numbered tape under
separator tape of the pair screen
*Upon request ; Black / White cores numbered 1-1, 2-2,…
PairTwo conductors twisted to a pair
Lay-upPIMF laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenAL-PES tape over tinned copper drain wire 0,50 mm2
BeddingPVC compund, TM1, BS 7655, Black
ArmourGalvenized round steel wire, BS EN 10257-1
Outer sheathPVC comp., flame retardant; TM1, BS 7655
Sheath colourRAL 9005, Black
Technical Data
StandardBS 5308 Part 2 Type 2
Insulation thickness0,50mm2 : 0,60mm
0,75mm2 : 0,60mm
1,50mm2 : 0,60mm
Conductor class, BS 63600,50mm2 : Class 5
0,75mm2 : Class 5
1,5mm2 : Class 2
Conductor resistance0,50mm2 : 39,7 Ω/km
0,75mm2 : 26,5 Ω/km
1,5mm2 : 12,3 Ω/km
Insulation resistanceMin. 25 MΩ.km
Mutual Capacitancemax. 250 pF/m
Capacitance unbalance(1 kHz) : max. 450 pF/250 m
L / R (ratio) (max.)0,50mm2 : 25 µH/Ω
0,75mm2 : 25 µH/Ω
1,5mm2 : 40 µH/Ω
Rated voltage300/500V
Test voltageUrms core-core : 1000 V
Urms core-screen : 1000 V
Temperature rangeoperation : - 40 oC ~ + 70 oC
ınstallation : - 5 oC ~ + 50 oC
Flame retardance testIEC 60332-1 & BS EN 60332-1
Min. bending radius6 x D
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1614 05 0022x2x0,50 12,016,833
1614 05 0055x2x0,5015,220,976
1614 05 01010x2x0,5021,127,9148
1614 05 01515x2x0,5024,531,3220
1614 05 02020x2x0,5027,334,3292
1614 05 03030x2x0,5032,340,5436
1614 05 05050x2x0,5041,751,5724
1614 06 0022x2x0,7512,817,648
1614 06 0055x2x0,7516,322,0112
1614 06 01010x2x0,7522,729,5220
1614 06 01515x2x0,7526,433,4328
1614 06 02020x2x0,7529,837,8436
1614 06 03030x2x0,7535,543,9652
1614 06 05050x2x0,7545,055,01084
1614 45 0022x2x1,5 14,720,471
1614 45 0055x2x1,518,825,4172
1614 45 01010x2x1,526,533,5340
1614 45 01515x2x1,530,838,8508
1614 45 02020x2x1,534,442,6676
1614 45 03030x2x1,541,050,81012
1614 45 05050x2x1,552,262,61684
Top 