background
TR  EN  DE  RU

Products

Back to products list
Birtaş Kablo
Instrumentation Cables BS 5308
RE-2Y(St)Y-fl-MP
RE-2Y(St)Y-fl-PIMF
RE-2Y(St)Y-fl
RE-2Y(St)Y-fl-TIMF
RE-2Y(St)2YSWAY-fl-MP
RE-2Y(St)2YSWAY-fl-PIMF
RE-2Y(St)2YSWAY-fl
RE-2Y(St)2YSWAY-fl-TIMF
RE-Y(St)Y-fl
RE-Y(St)Y-fl-MP
RE-Y(St)Y-PIMF
RE-Y(St)YSWAY-fl
RE-Y(St)YSWAY-fl-MP
RE-Y(St)YSWAY-PIMF
RE-2Y(St)H & RE-2X(St)H-MP
RE-2Y(St)H & RE-2X(St)H
RE-2Y(St)H-PIMF & RE-2X(St)H-PIMF
RE-2Y(St)H-TIMF & RE-2X(St)H-TIMF
RE-2Y(St)HSWAH & RE-2X(St)HSWAH
RE-2Y(St)HSWAH &
RE-2X(St)HSWAH-MP
RE-2Y(St)HSWAH-PIMF &
RE-2X(St)HSWAH-PIMF
RE-2Y(St)HSWAH-TIMF &
RE-2X(St)HSWAH-TIMF
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
MODERN CARTON
TÜPRAS
DOLPHIN PROJECT
ISKENDERUN STEEL
COLAKOGLU METALURJİ
PASABAHCE GLASS
INSTRUMENTATION CABLES BS5308
RE-Y(St)Y-fl-MP
INSTRUMENTATION CABLES, BS 5308 PART 2 TYPE 1
SİNGLE & MULTİ-PAİR, PVC INSULATED, COLLECTİVE SCREENED, PVC SHEATHED
Marking

BIRTAS KABLO RE-2Y(St)Y-fl MP 2 x 2 x 0.75mm2 1610 06 002 BS 5308 Part no GOST-R CE....mt

Applications

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

Cable Design
ConductorPlain annealed copper wire, BS 6360
0,50 mm2 and 0,75 mm2 flexible, or
1,5 mm2 stranded
InsulationPVC compound, TI1, BS 6746
Core identificationAccording to BS 5308 Part 2 colour coded
*Upon request ; Black / White cores numbered 1-1, 2-2,…
PairTwo conductors twisted to a pair
Lay-upPairs laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenAL-PES tape over tinned copper drain wire 0,50 mm2
Outer sheathPVC comp., flame retardant; TM1, BS 7655
Sheath colourRAL 9005, Black
Technical Data
StandardBS 5308 Part 2 Type 1
Insulation thickness0,50mm2 : 0,60mm
0,75mm2 : 0,60mm
1,50mm2 : 0,60mm
Conductor class, BS 63600,50mm2 : Class 5
0,75mm2 : Class 5
1,5mm2 : Class 2
Conductor resistance0,50mm2 : 39,7 Ω/km
0,75mm2 : 26,5 Ω/km
1,5mm2 : 12,3 Ω/km
Insulation resistanceMin. 25 MΩ.km
Mutual Capacitancemax. 250 pF/m
Capacitance unbalance(1 kHz) : max. 450 pF/250 m
L / R (ratio) (max.)0,50mm2 : 25 µH/Ω
0,75mm2 : 25 µH/Ω
1,5mm2 : 40 µH/Ω
Rated voltage300/500V
Test voltageUrms core-core : 1000 V
Urms core-screen : 1000 V
Temperature rangeoperation : - 40 oC ~ + 70 oC
ınstallation : - 5 oC ~ + 50 oC
Min. bending radius6 x D
Flame retardance testIEC 60332-1 & BS EN 60332-1
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1610 05 0011x2x0,507,01445
1610 05 0022x2x0,507,92470
1610 05 0055x2x0,5013,152165
1610 05 01010x2x0,5017,2100285
1610 05 01515x2x0,5019,8149400
1610 05 02020x2x0,5022,2196455
1610 05 03030x2x0,5026,9292740
1610 05 05050x2x0,5033,94841180
1610 06 0011x2x0,757,31950
1610 06 0022x2x0,758,33380
1610 06 0055x2x07514,377210
1610 06 01010x2x0,7518,7149360
1610 06 01515x2x0,7521,4221500
1610 06 02020x2x0,7524,5292670
1610 06 03030x2x0,7529,5437980
1610 06 05050x2x0,7537,47251560
1610 45 0011x2x1,58,33380
1610 45 0022x2x1,59,762135
1610 45 0055x2x1,516,4148310
1610 45 01010x2x1,521,6292550
1610 45 01515x2x1,525,2436820
1610 45 02020x2x1,528,55801030
1610 45 03030x2x1,534,38681525
1610 45 05050x2x1,543,614442490
Top 
Copyright © Etabir Birlesik Kablo Sanayi ve Ticaret A.S. - 2012. All rights reserved. design: plusmax