background
TR  EN  DE  RU

Products

Back to products list
Birtaş Kablo
Instrumentation Cables BS 5308
RE-2Y(St)Y-fl-MP
RE-2Y(St)Y-fl-PIMF
RE-2Y(St)Y-fl
RE-2Y(St)Y-fl-TIMF
RE-2Y(St)2YSWAY-fl-MP
RE-2Y(St)2YSWAY-fl-PIMF
RE-2Y(St)2YSWAY-fl
RE-2Y(St)2YSWAY-fl-TIMF
RE-Y(St)Y-fl
RE-Y(St)Y-fl-MP
RE-Y(St)Y-PIMF
RE-Y(St)YSWAY-fl
RE-Y(St)YSWAY-fl-MP
RE-Y(St)YSWAY-PIMF
RE-2Y(St)H & RE-2X(St)H-MP
RE-2Y(St)H & RE-2X(St)H
RE-2Y(St)H-PIMF & RE-2X(St)H-PIMF
RE-2Y(St)H-TIMF & RE-2X(St)H-TIMF
RE-2Y(St)HSWAH & RE-2X(St)HSWAH
RE-2Y(St)HSWAH &
RE-2X(St)HSWAH-MP
RE-2Y(St)HSWAH-PIMF &
RE-2X(St)HSWAH-PIMF
RE-2Y(St)HSWAH-TIMF &
RE-2X(St)HSWAH-TIMF
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
MODERN CARTON
TÜPRAS
DOLPHIN PROJECT
ISKENDERUN STEEL
COLAKOGLU METALURJİ
PASABAHCE GLASS
INSTRUMENTATION CABLES BS5308
RE-Y(St)Y-PIMF
INSTRUMENTATION CABLES, BS 5308 PART 2 TYPE 1
MULTİ-PAİR, PVC INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, PVC SHEATHED
Marking

BIRTAS KABLO RE-2Y(St)Y-PİMF 5 x 2 x 0.75mm2 1611 05 005 BS 5308 Part no GOST-R CE....mt

Applications

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. These cables are not recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

Cable Design
ConductorPlain annealed copper wire, BS 6360
0,50 mm2 and 0,75 mm2 flexible, or
1,5 mm2 stranded
InsulationPVC compound, TI1, BS 6746
Core identificationWhite / blue ; with numbered tape under
separator tape of the pair screen
*Upon request ; Black / White cores numbered 1-1, 2-2,…
PairTwo conductors twisted to a pair
PIMF ConstructionPolyester tape above the pair, AL-PES tape
over tinned copper drain wire, 0,50 mm2
Lay-upPIMF laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenAL-PES tape over tinned copper drain wire 0,50 mm2
Outer sheathPVC comp., flame retardant; TM1, BS 7655
Sheath colourRAL 9005, Black
Technical Data
StandardBS 5308 Part 2 Type 1
Insulation thickness0,50mm2 : 0,60mm
0,75mm2 : 0,60mm
1,50mm2 : 0,60mm
Conductor class, BS 63600,50mm2 : Class 5
0,75mm2 : Class 5
1,5mm2 : Class 2
Conductor resistance0,50mm2 : 39,7 Ω/km
0,75mm2 : 26,5 Ω/km
1,5mm2 : 12,3 Ω/km
Insulation resistanceMin. 25 MΩ.km
Mutual Capacitancemax. 250 pF/m
Capacitance unbalance(1 kHz) : max. 450 pF/250 m
L / R (ratio) (max.)0,50mm2 : 25 µH/Ω
0,75mm2 : 25 µH/Ω
1,5mm2 : 40 µH/Ω
Rated voltage300/500V
Test voltageUrms core-core : 1000 V
Urms core-screen : 1000 V
Temperature rangeoperation : - 40 oC ~ + 70 oC
ınstallation : - 5 oC ~ + 50 oC
Min. bending radius6 x D
Flame retardance testIEC 60332-1 & BS EN 60332-1
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1611 05 0022x2x0,5012,033125
1611 05 0055x2x0,5015,276220
1611 05 01010x2x0,5021,1148385
1611 05 01515x2x0,5024,5220560
1611 05 02020x2x0,5027,3292710
1611 05 03030x2x0,5032,3436980
1611 05 05050x2x0,5041,77241675
1611 05 0022x2x0,7512,848140
1611 05 0055x2x0,7516,3112260
1611 05 01010x2x0,7522,7220470
1611 05 01515x2x0,7526,4328675
1611 05 02020x2x0,7529,8436880
1611 05 03030x2x0,7535,56521295
1611 05 05050x2x0,7545,010842050
1611 45 0022x2x1,5 14,771195
1611 45 0055x2x1,518,8172370
1611 45 01010x2x1,526,5340675
1611 45 01515x2x1,530,8508990
1611 45 02020x2x1,534,46761255
1611 45 03030x2x1,541,010121850
1611 45 05050x2x1,552,516842990