RE-2Y(St)HSWAH-TIMF&RE-2X(St)HSWAH-TIMF HALOGEN-FREE INSTRUMENTATION CABLES, Acc. to BS 5308 PART 1 TYPE 2 RE-2Y(St)HSWAH-TIMF,SİNGLE & MULTİ-TRIPLE, PE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, ARMOUR, LSZH SHEATHED RE-2X(St)HSWAH-TIMF,SİNGLE & MULTİ-TRIPLE, XLPE INSULATED, INDIVIDUAL & COLLECTİVE SCREENED,ARMOUR, LSZH SHEATHED
Marking
BIRTAS KABLO RE-2X(St)HSWAH TİMF 2 x 3 x 0.50mm2 1630 11 002 BS 5308 Part no GOST-R CE....mt
Applications
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.
Cable Design
Conductor
Plain annealed copper wire, BS 6360 0,50 mm2 and 1,0 mm2 solid, 0,50 mm2 and 0,75 mm2 flexible or 1,5 mm2 stranded
Insulation (2Y)
PE compound, BS 6234 Type03 (RE-2Y….)
Insulation (2X)
XLPE compound, GP8, BS 7655 (RE-2X….)
Core identification
Black / White / Red; with numbered tape under separator tape of the pair screen *Upon request ; Black / White / Red cores numbered 1-1-1, 2-2-2,…
Triple
Three conductors twisted to a triple
TIMF Construction
Polyester tape above the triple, AL-PES tape over tinned copper drain wire, 0,50 mm2
Lay-up
TIMF laid up in layers of optimum pitch
Separator
Polyester tape
Screen
AL-PES tape over tinned copper drain wire 0,50 mm2