Halogen Free Installation & Energy Cables
H05Z-U & H07Z-U/R & H05Z/K & H07Z/K
H05Z1-U & H07Z1-U/R & H05Z1/K & H07Z1/K
H03Z1Z1-F 300/300 V & H05Z1Z1-F 300/500 V
NHMH
NHXMH
N2XH
N2XCH
NHXMH FE180
N2XH FE180
(N)2GH FE180
(N)2GH FE180 - FLEX
(N)HXH FE180 E30
(N)HXH FE180 E90
(N)HXCH FE180 – E30
(N)HXCH FE180 – E90
Cu/XLPE/LSZH/SWA/LSZH – MULTICORE – BS 6724
2XHRH
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
ISTINYE PARK SHOPPING CENTER
KORUPARK SHOPPING CENTER
FORUM MERSİN SHOPPING CENTER
CEPA SHOPPING CENTER
KANYON SHOPPING CENTER
ISTANBUL TEKSTİLKENT
HALOGEN FREE INSTALLATION & ENERGY CABLES
(N)HXCH FE180 - E30
HALOGEN-FREE, SCREENED ENERGY SAFETY CABLES, 0,6/1 kV
Marking

BIRTAS KABLO (N)HXH FE 180 E 30 4 x 25 (rm)/16 mm2 1996 51 004 Part no GOST-R CE … mt

Applications

These halogen-free, screened cables fields of use are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power under the existing fire conditions. These halogen-free safety cables are used as energy, utility and lighting cables in dry, moist and wet rooms, for permanent installation above, on, in and under beneath plaster and also for outdoor applications where lots of human life and material assets are to be protected in industrial constructions, schools, hospitals, shopping and cultural centers,energy plants, airports, metros . In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

Cable Design
ConductorCu wires,plain, solid-core, multi-stranded
IEC 60228 Cls. 1/2, TS/DIN EN 60228 Cls. 1/2
InsulationCeramifiable cross-linked elastomer
compound, HXI1, VDE 0266
Core identificationAccording to TS HD 308 S2 & VDE 0293-308;
Note: Other core configurations manufactured upon request.
Lay-upCores laid up in layers of optimum pitch
WrappingFiber glass textile tape
Concentric conductorPlain copper wires with a traverse spiral of
copper tape
Outer sheathHFFR compound, HM4, VDE 0276-604
HFFR: Halogen-free flame retardant
Sheath colourRAL 2003, Orange or RAL 9005, Black
Technical Data
StandardDIN VDE 0266 & TS HD 604 S1
(Designed according to)
Temp. at conductor90 oC
Rated voltage0,6 / 1 kV
Test voltage4000 V
Temperature rangeFixed: - 30 oC ~ + 90 oC
Mobile: - 5 oC ~ + 50 oC
Min. bending radiusSıngle-core: 15 x D
Multi-core: 12 x D
Smoke density testIEC 61034-2 & TS/DIN EN 61034-2
Halogen-free properties testIEC60754-1/2 & TS/DIN EN 50267-2
Flame testIEC 60332-3 & TS/DIN EN 50266-2-4
Insulation integrityIEC 60331 , VDE 0472-814
System circuit integrityDIN 4102-12; E30
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1996 15 0022x1,5 re/1,510,652170
1996 15 0033x1,5 re/1,511,166185
1996 15 0044x1,5 re/1,511,981210
1996 16 0022x2,5 re/2,511,480215
1996 16 0033x2,5 re/2,511,9104240
1996 16 0044x2,5 re/2,512,8125280
1996 17 0011x4 re8,839105
1996 18 0011x6 re9,358130
1996 19 0011x10 re10,796195
1996 50 0011x16 rm12,3154280
1996 17 0022x4 re/411,6123290
1996 17 0033x4 re/413,2161330
1996 18 0022x6 re/613,6182370
1996 17 0044x4 re/414,8200395
1996 51 0011x25 rm15,0240400
1996 18 0033x6 re/614,8240440
1996 18 0044x6 re/616,0297525
1996 19 0022x10 re/1016,7312535
1996 19 0033x10 re/1017,5408640
1996 19 0044x10 re/1019,3504795
1996 50 0022x16 rm/1620,4489805
1996 50 0033x16 rm/1621,5643975
1996 50 0044x16 rm/1623,47961200
1996 51 0022x25 rm/1624,27601210
1996 51 0033x25 rm/1625,510031350
1996 51 0044x25 rm/1628,011421780