background
TR  EN  DE  RU

Kabel Produkte

Zurück zur Produkt Liste
Birtas Kabel - Birtaş – Marktführer von Industrie- und Spezialkabeln bis 1kV in der Türkei
Instrumentenkabel
500V PVC D.K. PVC -70 +150 Grad
RE-Y(St)Y-fl & RE-Yw(St)Yw-fl MP
RE-Y(St)Y-fl & RE-Yw(St)Yw-fl
RE-Y(St)Y-fl-PIMF &
RE-Yw(St)Yw-fl-PIMF
RE-Y(St)Y-fl-TIMF &
RE-Yw(St)Yw-fl-TIMF
RE-Y(St)YSWAY-fl &
RE-Yw(St)YwSWAYw-fl MP
RE-Y(St)YSWAY-fl &
RE-Yw(St)YwSWAYw-fl
RE-Y(St)YSWAY-fl-PIMF &
RE-Yw(St)YwSWAYw-fl-PIMF
RE-Y(St)YSWAY-fl-TIMF &
RE-Yw(St)YwSWAYw-fl-TIMF
Downloads
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Beispiel Referenzen
MODERN CARTON
TÜPRAS
DOLPHIN PROJECT
ISKENDERUN STEEL
COLAKOGLU METALURJİ
PASABAHCE GLASS
INSTRUMENTENKABEL
500V PVC D.K. PVC -70 +150 GRAD
RE-Y(St)YSWAY-fl & RE-Yw(St)YwSWAYw-fl MP
INSTRUMENTATION CABLES, EN 50288-7
SINGLE & MULTI-PAIR, PVC INSULATED, COLLECTIVE SCREENED, ARMOURED, PVC SHEATHED
Beschriftung

BIRTAS KABLO RE-Y(St)YSWAY-fl MP 4 x 2 x 1mm2 1695 43 004 500 VEN 50288-7 -70 / +150° C Part no GOST-R CE....mt

Anwendung

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. For application of 105oC heat resistant, RE-Yw(St)YwSWAYw cables are suitable. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

Kabel Design
ConductorPlain copper wire, stranded
IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation (Y)PVC compound, 70 oC grade; EN 50290-2-21
Insulation (Yw)PVC compound, 105 oC grade; EN 50290-2-21
Core identificationBlack / Blue cores numbered 1-1, 2-2,…
Upon request ; Colour coded according to IEC 60189-2
Other core configurations manufactured upon request.
PairTwo conductors twisted to a pair
Lay-upPairs laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenAL-PES tape over stranded tinned copper drain
wire 0,50 mm2
Inner sheath (Y)PVC compound, 70OC grade; EN 50290-2-22
Inner sheath (Yw)PVC compound, 105OC grade; EN 50290-2-22
ArmourGalvenized round steel wire, EN 10257-1
Outer sheath (Y)PVC compound, 70 oC grade; EN 50290-2-22
Outer sheath (Yw)PVC compound, 105 oC grade; EN 50290-2-22
Sheath colourRAL 9005, Black or RAL 5015, Blue
Technische Daten
StandardTS/DIN EN 50288-7
Conductor resistance0,50mm2 : 36,7 Ω/km
0,75mm2 : 25,0 Ω/km
1,0mm2 : 18,5 Ω/km
1,3mm2 : 14,2 Ω/km
1,5mm2 : 12,3 Ω/km
Insulation resistanceMin. 100 MΩ.km
Mutual Capacitance0,50 mm2 : max. 160 pF/m ≤ 4 pairs,max. 120 pF/m all other pairs
0,75 mm2 : max. 160 pF/m ≤ 4 pairs,max. 120 pF/m all other pairs
1,0 mm2 : max. 160 pF/m ≤ 4 pairs,max. 120 pF/m all other pairs
1,3 mm2 : max. 170 pF/m ≤ 4 pairs,max. 130 pF/m all other pairs
1,5 mm2 : max. 170 pF/m ≤ 4 pairs,max. 130 pF/m all other pairs
Capacitance unbalance (1 kHz) : max. 500 pF/500 m
L / R (ratio) (max.)0,50mm2 : 25 µH/Ω
0,75mm2 : 25 µH/Ω
1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω
1,5mm2 : 40 µH/Ω
Rated voltage500V
Test voltageUrms core-core : 2000 V
Urms core-screen : 2000 V
Temperature range (2Y)operation : - 30 oC ~ + 70 oC
ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X)operation : - 30 oC ~ + 105 oC
ınstallation : - 5 oC ~ + 50 oC
Min. bending radius10 x D
Flame retardance testIEC 60332-1 & EN 60332-1
Querschnitt
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1695 41 001 (RE-Y(St)YSWAY-fl)1x2x0,5010,814205
1695 41 002 (RE-Y(St)YSWAY-fl)2x2x0,5013,824300
1695 41 004 (RE-Y(St)YSWAY-fl)4x2x0,5015,543380
1695 41 005 (RE-Y(St)YSWAY-fl)5x2x0,5016,053415
1695 41 006 (RE-Y(St)YSWAY-fl)6x2x0,5016,862455
1695 41 008 (RE-Y(St)YSWAY-fl)8x2x0,5018,382525
1695 41 010 (RE-Y(St)YSWAY-fl)10x2x0,5019,8101605
1695 41 012 (RE-Y(St)YSWAY-fl)12x2x0,5021,7120780
1695 41 016 (RE-Y(St)YSWAY-fl)16x2x0,5024,0158930
1695 41 020 (RE-Y(St)YSWAY-fl)20x2x0,5025,81971060
1695 41 024 (RE-Y(St)YSWAY-fl)24x2x0,5027,72351195
1695 42 001 (RE-Y(St)YSWAY-fl)1x2x0,7511,219225
1695 42 002 (RE-Y(St)YSWAY-fl)2x2x0,7514,434330
1695 42 004 (RE-Y(St)YSWAY-fl)4x2x0,7516,362430
1695 42 005 (RE-Y(St)YSWAY-fl)5x2x0,7516,877465
1695 42 006 (RE-Y(St)YSWAY-fl)6x2x0,7517,891515
1695 42 008 (RE-Y(St)YSWAY-fl)8x2x0,7519,6120610
1695 42 010 (RE-Y(St)YSWAY-fl)10x2x0,7521,7149805
1695 42 012 (RE-Y(St)YSWAY-fl)12x2x0,7523,2178905
1695 42 016 (RE-Y(St)YSWAY-fl)16x2x0,7525,52351075
1695 42 020 (RE-Y(St)YSWAY-fl)20x2x0,7527,82931250
1695 42 024 (RE-Y(St)YSWAY-fl)24x2x0,7530,03501435
1695 43 001 (RE-Y(St)YSWAY-fl)1x2x111,824245
1695 43 002 (RE-Y(St)YSWAY-fl)2x2x115,143360
1695 43 004 (RE-Y(St)YSWAY-fl)4x2x117,182475
1695 43 005 (RE-Y(St)YSWAY-fl)5x2x117,7101520
1695 43 006 (RE-Y(St)YSWAY-fl)6x2x118,7120575
1695 43 008 (RE-Y(St)YSWAY-fl)8x2x121,4158795
1695 43 010 (RE-Y(St)YSWAY-fl)10x2x123,2197915
1695 43 012 (RE-Y(St)YSWAY-fl)12x2x124,62351025
1695 43 016 (RE-Y(St)YSWAY-fl)16x2x127,33121235
1695 43 020 (RE-Y(St)YSWAY-fl)20x2x129,93891460
1695 43 024 (RE-Y(St)YSWAY-fl)24x2x132,84661830
1695 44 001 (RE-Y(St)YSWAY-fl)1x2x1,312,330265
1695 44 002 (RE-Y(St)YSWAY-fl)2x2x1,316,155410
1695 44 004 (RE-Y(St)YSWAY-fl)4x2x1,318,1105535
1695 44 005 (RE-Y(St)YSWAY-fl)5x2x1,318,8130590
1695 44 006 (RE-Y(St)YSWAY-fl)6x2x1,320,8155765
1695 44 008 (RE-Y(St)YSWAY-fl)8x2x1,323,0204915
1695 44 010 (RE-Y(St)YSWAY-fl)10x2x1,324,72541045
1695 44 012 (RE-Y(St)YSWAY-fl)12x2x1,326,33041170
1695 44 016 (RE-Y(St)YSWAY-fl)16x2x1,329,74041460
1695 44 020 (RE-Y(St)YSWAY-fl)20x2x1,333,05041875
1695 44 024 (RE-Y(St)YSWAY-fl)24x2x1,335,46042130
1695 45 001 (RE-Y(St)YSWAY-fl)1x2x1,512,634280
1695 45 002 (RE-Y(St)YSWAY-fl)2x2x1,516,762430
1695 45 004 (RE-Y(St)YSWAY-fl)4x2x1,518,8120570
1695 45 005 (RE-Y(St)YSWAY-fl)5x2x1,519,7149640
1695 45 006 (RE-Y(St)YSWAY-fl)6x2x1,521,5178820
1695 45 008 (RE-Y(St)YSWAY-fl)8x2x1,523,8235980
1695 45 010 (RE-Y(St)YSWAY-fl)10x2x1,525,72931125
1695 45 012 (RE-Y(St)YSWAY-fl)12x2x1,527,53501275
1695 45 016 (RE-Y(St)YSWAY-fl)16x2x1,531,84661755
1695 45 020 (RE-Y(St)YSWAY-fl)20x2x1,534,55812045
1695 45 024 (RE-Y(St)YSWAY-fl)24x2x1,536,96962305