J-H(St)H Lg FE180 E30/E90 HALOGEN-FREE FIRE ALARM INSTALLATION CABLE
Beschriftung
BIRTAS KABLO J-H(St)H…Lg FE180 E30/E 90 40 x 2 x 0.60mm 1920 03 040 / Ex PROOF TS 3164 IEC 60331 Part no GOST-R CE ... mt.
Anwendung
These cables fields of use are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power for a period of 180 minutes under the existing fire conditions (at a temperature of 750OC and under the flames ). Also these cables shall satify EN50200 test which is a fire resistant with mechancal shock test (under the conditions at 842oC and mechenical shock) by the classes PH15-PH30-PH60-PH90. And also the test of DIN 4102-12, E30 and E90 which is a sysyem test with all components and cables to satisfy the system circuit integrity. hese halogen-free cables are used for fire alarm systems, signal and data communications as an fixed indoor installations. And also screen provides protection against external pulses . These cables are used at schools, airpots, hospitals, etc. and in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Kabel Design
Pair
Two conductors twisted to a pair
Lay-up
Cores laid up in layers of optimum pitch
Separator
Polyester tape
Wrapping
Fiber glass textile tape
Screen
With drain wire under the AL-PES tape Drain wire; Phi: 0,40 mm ≤10 pairs Phi:0,60 mm > 10 pairs
Outer sheath
HFFR compound, HM4, VDE 0207-24
Sheath colour
RAL 3000, Red
Technische Daten
Standard
VDE 0815 (Designed according to)
Insulation resistance
Min. 100 MΩ.km
Mutual Capacitance
Max. 100 nF/km *This value may be exceeded by 20% by cables with up to 4 pairs
Capacity Unbalanced
Max. 300 pF / 100 mt *20% of the values, at least one value up to 400 pF permitted